Installing manifolds and connecting pipes
The "Layout" section of the main toolbar contains the options for adding manifolds and the pipes connecting the manifolds to the circuits:

Manifold
Defines a manifold and positions it in the workspace by selecting a point on the floor plan.
When you enter a manifold, the program requires you to define the following parameters. If a value is locked, it will not be modified when the results are updated, but will remain unchanged:
- Reference
Manifold reference. - Number of circuits (Lock/Unlock)
Number of circuits associated with the collector. - Pipe length (optional)
Additional pipe length on the manifold. - Flow temperature
Sets the flow temperature for heating and cooling:- Heating
- Refrigeration
- Hydraulic balancing
Selects one of the following:- Static balancing valve
Selects the type of static balancing valve. Valve types can be created and edited using the options available to the right of the drop-down menu or via the libraries available under "General options" within the "Project" group. - Flow meter
- Static balancing valve
- Pressure loss (optional)
- Hydraulic balancing
- Kv
Enters the flow coefficient (Kv) directly. - Equation (ΔP = a·Qm + b·Qn + c·Qk)
This equation is used to define the parameters a, b, c, m, n and k that relate the pressure drop (ΔP) in kPa to the flow rate (Q) in l/h.
- Kv
- Hydraulic balancing

Connection pipe
This allows the connection pipes between the manifold and the connection points of the underfloor heating circuits to be installed.
When entering the connection pipe, the program requires the following parameters to be defined:
- Step
- Radius of curvature