CYPETHERM. "Systems" tab – Performance curves

Share
Associated programs

Performance curves

The performance of heating and cooling systems varies depending on operating conditions. When carrying out an energy simulation using the EnergyPlus™ calculation engine, the program can account for this variation in two ways:

  • By selecting the behaviour curves included by default for each piece of equipment. To do this, select the "Default" option when editing the behaviour curves for each piece of equipment.
  • By editing the performance curves of the hydronic production equipment (boilers and chillers). To do this, select the "User-defined" option when editing the performance curves for each piece of equipment. The program offers two options for entering this data: in table form or as a polynomial curve.

User-defined performance curves for chillers

Rated conditions

Rated conditions are the operating conditions under which the rated characteristics of the equipment are defined.

Performance curves must be defined in such a way that, under rated conditions, their value is equal to 1.

All performance curves for a single piece of equipment must be defined for the same rated conditions.

  • Water temperature at chiller outlet
  • Fluid temperature at condenser inlet

CapFT curve

Cooling capacity correction factor. The "Curve description" can be defined "By points" or using a polynomial equation ("By equation").

EIRFT curve

Power consumption correction factor. The "Curve description" can be defined "By points" or using a polynomial equation ("By equation").

EIRFPLR curve

Power consumption correction factor. The "Curve description" can be defined "By points" or using a polynomial equation ("By equation").

Chiller performance curves (point-by-point definition)
Performance curves for chillers (defined by equation)

User-defined boiler performance curves

Nominal conditions

Rated conditions are the operating conditions under which the rated characteristics of the equipment are defined.

Performance curves must be defined in such a way that, under nominal conditions, their value is equal to 1.

All performance curves for a single piece of equipment must be defined for the same nominal conditions.

  • Water temperature (Boiler inlet / Boiler outlet)
  • Partial load factor (PLR)
    It is equal to 1.

EffFPLRT curve

Efficiency correction factor. The "Curve description" can be defined "By points" or using a polynomial equation ("By equation").

Boiler performance curve (point-by-point definition)
Boiler performance curve (defined by an equation)