Water-air conditioning systems
Water-air conditioning systems include equipment such as boilers, chillers and air-source heat pumps, as well as the distribution network for hot or cold water. The terminal units that can be connected to these systems include radiators, underfloor heating and fan coils.
Chilled-water system
The definition of a chilled-water system comprises two sections: "Cold water production equipment" and "Cold water distribution".
Cold water production equipment (chillers)
This section defines the chilled water production units (chillers) connected in parallel to the chilled water distribution network. A maximum of 10 units may be installed.
- Reference
Equipment reference. - Refrigeration
- Rated capacity (optional)
- Sizing factor
If a power value has not been specified, the unit’s power will be determined by multiplying the zone’s heat load by this factor.
- Sizing factor
- Nominal cooling COP
- Rated capacity (optional)
- Condenser
- Condenser type (Air-cooled / Water-cooled / Evaporatively cooled)
- Operating parameters
- Leaving chilled water lower temperature limit
- Minimum part load ratio
This is the ratio of the minimum power to the rated power of the equipment. Below this load value, the equipment operates by switching on and off. - Maximum part load ratio
This is the ratio of the maximum power to the rated power of the equipment. If it is greater than 1, the equipment is capable of handling loads in excess of its rated power. - Optimum part load ratio
This is the ratio between the power that the unit is capable of generating and the rated power that ensures maximum efficiency. This figure is only relevant if there is more than one unit and the "Operating parameters" specify that loads should be distributed taking this optimum ratio into account. - Minimum compressor unloading ratio
- Performance curves
- By default
- Electric centrifugal chiller / Electric screw chiller / Reciprocating compressor chiller
- User-defined
- By default
Cold water supply
This section sets out the design and operating parameters for the cold water distribution network and the circulation pump.
- Design parameters
These parameters are used to automatically calculate the flow rate of the cold water circuit.- Design setpoint temperature
- Design temperature range
- Fluid type (Water / Ethylene glycol / Propylene glycol)
- Circulation pump
- Control (Intermittent / Continuous)
- Intermittent
If the control is intermittent, the pump switches on and off in time with the system. - Continuous
If the control is continuous, the pump is always running, even when there is no demand. During long periods without demand, heat losses from the pump accumulate in the fluid, which can cause a noticeable rise in its temperature.
- Intermittent
- Configuration (Constant primary, no secondary / Variable primary, no secondary / Constant primary, variable secondary)
- Primary loop pump type (Single pump / One pump per chiller / Two pumps in parallel / Three pumps in parallel / Four pumps in parallel / Five pumps in parallel)
- Primary loop pump rated head
- Control (Intermittent / Continuous)
- Operating parameters:
- Minimum outdoor temperature
Below this temperature, the production units will not switch on, even if there is demand in the zones. - Load distribution scheme (Optimal / Sequential load / Uniform load / Uniform PLR / Sequential uniform PLR)
You can control the activation of production equipment.- Optimal
The units share the load sequentially until the optimal partial load ratio (PLR) specified for each generator is reached. - Sequential load
The devices switch on one after the other, in the order listed, until the charge is complete. - Uniform PLR
The equipment shares the load equally. - Uniform partial load ratio
The equipment shares the load in proportion to its rated power. - Uniform sequential partial load ratio The number of units required to handle the load is determined, and the load is distributed amongst them in proportion to their rated power. The remaining units remain switched off.
- Optimal
- Setpoint temperature control (Design setpoint temperature / Outdoor air temperature reset)
The setpoint temperature specified in this section will be used during the simulation.
- Minimum outdoor temperature
- Piping system configuration
Bypass pipes regulate the circuit’s power in the simulation. They perform the same function as valves in a real-world installation. We recommend that you do not disable these options.- Supply-side bypass pipe (optional)
- Demand-side bypass pipe (optional)
Water-based heating system
The definition of water-based heating systems comprises two sections: "Hot water production equipment" and "Hot water distribution".
Hot water production equipment
This section defines the hot water production units connected in parallel to the hot water distribution network. A maximum of 10 units may be installed.
The program offers two types of hot water production equipment: boilers and air-to-water heat pumps.
Boiler
- Reference
Equipment reference number. - Heating
- Rated capacity (optional)
Specify a value for the boiler’s rated power.- Sizing factor
If no power value has been specified, the unit’s power will be determined by multiplying the zone’s heat load by this factor.
- Sizing factor
- Rated efficiency
If the performance curve is not defined, the boiler’s efficiency value, measured under the following nominal conditions, must be specified:- Conventional boiler: water outlet at 82°C / Condensing boiler: water inlet at 70°C.
- Fuel type (Electricity / Natural gas / LPG / Heavy fuel oil / Coal / Biomass / Densified biomass (pellets))
- Rated capacity (optional)
- Operating parameters:
- Water outlet upper temperature limit
- Minimum part load ratio
This is the ratio of the minimum power to the rated power of the equipment. Below this load value, the equipment operates by switching on and off. - Maximum part load ratio
This is the ratio of the maximum power to the rated power of the equipment. If it is greater than 1, the equipment is capable of handling loads in excess of its rated power. - Optimum part load ratio
This is the ratio between the power that the unit is capable of generating and the rated power, which ensures greater efficiency. This figure is only relevant if more than one unit is available and the "Operating parameters" specify that loads should be distributed taking this optimum ratio into account.
- Performance curves
- By default
- Conventional boiler / Condensing boiler
- User-defined
- By default
Air-to-water heat pump
- Reference
Equipment reference number. - Heating
- Rated capacity (A7W35) (optional)
Specify a value for the rated power of the air-to-water heat pump.- Sizing factor
If no power value has been specified, the unit’s power will be determined by multiplying the zone’s heat load by this factor.
- Sizing factor
- Gross rated heating COP (A7W35)
- Rated capacity (A7W35) (optional)
Hot water supply
This section sets out the design and operating parameters for the hot water distribution system and the circulation pump.
- Design parameters
These parameters are used to automatically calculate the flow rate of the hot water circuit.- Design setpoint temperature
- Design temperature range
- Fluid type (Water / Ethylene glycol / Propylene glycol)
- Circulating pump
- Control (Intermittent / Continuous)
- Intermittent
If the control is intermittent, the pump switches on and off in time with the system. - Constant flow
If the control is continuous, the pump is always running, even when there is no demand. During long periods without demand, heat losses from the pump accumulate in the fluid, which can cause a noticeable rise in its temperature.
- Intermittent
- Configuration (Variable flow / Constant flow)
- Primary circuit pump type (Single pump / One pump per boiler / Two pumps in parallel / Three pumps in parallel / Four pumps in parallel / Five pumps in parallel)
- Rated head
- Control (Intermittent / Continuous)
- Operating parameters:
- Maximum outdoor temperature
Above this temperature, the production units will not switch on, even if there is demand in the zones. - Load distribution scheme (Optimal / Sequential load / Uniform load / Uniform partial load ratio / Sequential uniform partial load ratio)
You can control the activation of production equipment.- Optimal
The units share the load sequentially until the optimal partial load ratio (PLR) specified for each generator is reached. - Sequential load
The devices are switched on one after the other, in the order listed, until the charge is complete. - Uniform load
The teams share the workload equally. - Uniform PLR
The units share the load in proportion to their rated power. - Sequential uniform PLR
The number of units required to handle the load is determined, and the load is distributed amongst them in proportion to their rated power. The remaining units remain switched off.
- Optimal
- Setpoint temperature control (Design setpoint temperature / Outdoor air temperature reset)
The setpoint temperature specified in this section will be used during the simulation.
- Maximum outdoor temperature
- Pipe network configuration
Bypass pipes regulate the circuit’s power in the simulation. They perform the same function as valves in a real-world installation. We recommend that you do not disable these options.- Supply-side bypass pipe (optional)
- Demand-side bypass pipe (optional)
Air-source heat pump system
Select an air-source heat pump system from the manufacturers and models available in the Open BIM Database, which have been downloaded beforehand via the "Catalogues" option on the main interface.
You must select whether it is a "Monobloc", "Bibloc" or "Hydraulic Bibloc" system.
Heating
These parameters are used to automatically calculate the flow rate of the water circuit.
- Design setpoint temperature
- Design delta temperature
Cooling (optional depending on model)
These parameters are used to automatically calculate the flow rate of the water circuit.
- Design setpoint temperature
- Design delta temperature
Operating mode (month by month)
- Heating / Cooling (optional) / Off
Geothermal heat pump
Select a geothermal heat pump from the manufacturers and models available in the Open BIM Database, which have been downloaded beforehand via the "Catalogues" option on the main interface.
Heating
These parameters are used to automatically calculate the flow rate of the water circuit.
- Design setpoint temperature
- Design delta temperature
Cooling (optional depending on model)
These parameters are used to automatically calculate the flow rate of the water circuit.
- Design setpoint temperature
- Design delta temperature
Geothermal circuit
Select a water-cooled condensing system with a specified temperature, as set out in the "Air-conditioning systems" section.
- Water-cooled system
Operating mode (month by month)
- Heating / Cooling (optional) / Off